Tube Mill
Consolidated Pulpit Project
JNE Automation’s scope of work involved modifying the Tube Mill automation system to accommodate the
installation of a new pulpit combining the controls of two separate stations in the mill. The pulpit did not
replace the two stations; instead the stations were mirrored, allowing an operator to control the process
from either the pulpit or the local stations. The two mirrored stations were the High Frequency Welder
station (Mill) and the Flying Saw station. Each local station has a control desk consisting of pushbuttons and
indicator lamps as well as an Allen Bradley PanelView 1400e HMI. The new Mill and Flying Saw control
desks were mirrored separately and the two PanelView 1400e’s were mirrored using one AB PanelView Plus
1250 terminal in the new pulpit.
PLC Changes
The project required signals to and from the existing local desks and signals to and from the PanelViews to
be mirrored in the PLC code. The mirroring required code in three processors to be modified to ensure that the
new and existing desks controlled the process properly. The existing processors were AB Control Logix 5000
and the PLC code was modified using RS Logix 5000 Enterprise software. The new desks were connected to
an existing ControlNet network using Flex IO racks, ControlNet adapters (1794-ACN15/C) and ControlNet
bridges (1756-CNB/B). New Flex IO modules, the 1794-IB16/A 16 point 24V DC Input and the 1794-OA16/A
120V AC output, were added to a rack to accommodate the new inputs and outputs. Two racks were added,
one for the mirrored Mill controls and one for the mirrored Flying Saw controls.
HMI Changes
The two AB PanelView 1400e stations running PanelBuilder software were mirrored in the new pulpit using
one PanelView Plus 1250 running RSView Enterprise Machine Edition (ME). Using the conversion tool
supplied with RSView ME, the old PanelBuilder 1400e screens were imported into the ME environment. The
conversion process was approximate and therefore required changes to most of the screens and menu
systems that were included in the old terminals. Communication with the PLC was achieved via a ControlNet
Adapter Module (2711P-RN15S) attached to the HMI using the 1789-A17 Virtual Chassis. New programs are
downloaded to the PanelView Plus 1250 using ControlNet and RS Linx Enterprise.
JNE Automation was responsible for:
- Engineering design
- Hardware specifications and procurement
- Creation and modification of electrical schematics
- HMI programming (using RSView Enterprise ME)
- PLC programming (using RSLogix5000)
- Network configuration (using RSNetworx for ControlNet)
- System commissioning
|